Tecnichal data
| Number of auxiliary contacts as normally open contact | 0 |
| Number of auxiliary contacts as normally closed contact | 0 |
| Vibration resistance | IEC 60068-2-6 |
| Shock resistance | IEC 60068-2-27 |
| Altitude, max | 3000 m of installation site |
| Switching frequency, max | 600 ops/hr, AC-1 |
| Weight | AC/DC (electronic): 1.23 kg (2.7 lbs.) |
| Protection class | Contactor main contact: IP2X (100-E40…E96 meet IP2X when used with 100-ESC…terminal shrouds.) |
| Voltage type for actuating | AC/DC |
| Rated control supply voltage at AC 50 Hz | 250 V |
| Rated control supply voltage at AC 60 Hz | 250 V |
| Rated control supply voltage at DC | 250 V |
| Type of electrical connection of main circuit | Screw connection |
| Rated impulse voltage withstand (Uimp) | 6 kV |
| Operating time, closing delay | 42 ms |
| Operating time, opening delay | 17 ms |
| Optional overload relays | Electronic |
| Main current circuit resistance | 0.16 mé |
| Rated isolation voltage (Ui) | 690V per IEC |
| Function | Non-reversing contactor |
| Standard coil, pick-up | 25VA/25 W @ 250…500V AC/DC |
| Standard coil, hold-in | 4VA/2 W @ 250…500V AC/DC |
| General purpose current (enclosed) | 34 A @ 600V per UL/CSA |
| Power dissipation | 7.6 W per pole at Ie, AC-1, 400V |
| Short time withstand (Icw) | 3-pole: 780 A for 10 s (40 ðC) |
| FLA | 80 A @ 600V, 3-phase per UL/CSA HVAC applications |
| Rated operational current and power (enclosed) | 7.5 Hp @ 125V DC, with 3-poles in series per UL/CSA |
| LRA | 480 A @ 440-480V AC, 3-phase per UL/CSA HVAC applications |
| Electromagnetic compatibility | IEC 60947-1 – Environment A and B (100-E09…E38 only.) |
| Total power dissipation | 11 W at Ie, AC-3, 400V, AC/DC control (120-250V) |
| Operating limits, dropout | (ââ°¤0.60) x Us @ DC control |
| Rating for switching AC motors | 3-poles: 50 Hp @ 575V, AC-2, AC-3 (60 Hz) |
| Operating limits, pick-up | (0.85…1.1) x Us @ 50/60 Hz |
| MCCB current rating | Type 2 (per IEC 60947-4-1): 800 A @ 400 V, 70 kA available fault current |
| DIN fuses (gG) current rating | Type 2 (per IEC 60947-4-1): 63 A @ 690 V, 60 kA available fault current |
| Rated voltage (Ue) | 24V, 48V, 110V, 220V, 440V DC |
| Rated operational current and power | 7.5 Hp @ 230V AC, 500000 electrical operations, 1-phase per UL/CSA elevator duty |
| Coil voltage | 250 to 500V AC/DC |
| Switching of lighting loads | Tungsten lamps: 80 A @ 600V, 3-phase (break all lines) per UL/CSA |
| UL class RK5 fuses rating | Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 150 A @ 600V, 5 kA available fault current |
| Rated operational current (Ie) | 80 A @ 690V, AC-1 active power load (50/60 Hz), ambient temperature 60 ðC (140 ðF) |
| UL class J and CSA HRCI-J fuses rating | Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 150 A @ 600V, 100 kA available fault current |
| UL inverse-time circuit breaker | Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 250 A @ 600V, 5 kA available fault current |
| Switching of power transformers | Apparent power: 86 kVA @ 480V, 60 Hz (n = 15) |
| Rated operational power (Pe) | 96 kW @ 690V, AC-1 active power load (50/60 Hz), ambient temperature 60 ðC (140 ðF) |
| Switching of DC loads | 3-poles in series: 100 A @ 220V (Shunt-wound motors starting, reverse current breaking, reversing, stepping DC-3 at 60 ðC) |
| Optional accessories | Side-or front-mount auxiliary contacts, Mechanical interlocks, IP20 terminal shields, Connecting bars |
| Features | Panel mounting or mounting on 35 mm DIN rail, AC/DC electronic coil, Made of environmentally friendly materials |
| Climatic withstand | Category B according to IEC 60947-1, annex Q |
| Ambient temperature | Storage: -60…80 ðC (-76…176 ðF) |
| Coil insulation class | Class F per IEC 60947-4-1 |