Tecnichal data
| Number of outputs, safety related, undelayed, with contact | 2 |
| Number of outputs, signalling function, undelayed, with contact | 0 |
| Number of outputs, safety related, undelayed, semiconductors | 0 |
| Number of outputs, signalling function, undelayed, semiconductors | 0 |
| Number of outputs, signalling function, delayed, semiconductors | 0 |
| With start input | Yes |
| With muting function | No |
| Voltage type for actuating | AC |
| Rated control supply voltage at DC | 0 V |
| Model | Basic device |
| Type of electric connection | Screw connection |
| Evaluation inputs | One- and two-channel |
| Power ON delay | 300 ms |
| Input resistance, max | 90 Ohm |
| Power consumption | 4 W |
| Terminal type | Fixed |
| Operating voltage range | 97.75 V |
| Inductive, AC-15 | 6.0 A @ 250V AC |
| Inductive, DC-13 | 6 A/24V DC @ 6 ops/min |
| Fuses output | External: 6 A slow blow or 10 A quick blow |
| Rated thermal current (Ith) | Maximum 6 A in one current path (non-switching) |
| Continuous safety output current | UL: B300, 5 A @ 250V AC, 24V AC, 6 A @ 24V DC, AC-15: 6 A @ 250V AC, DC-13: 3 A @ 24V DC |
| Wire size | 0.2…2.5 mmò (24…12 AWG) |
| Electrical life cycle | Operations: 100.000 (220V AC / 4 A / 880VA cosÃâ= 0.35), 500.000 (220V AC / 1.7 A / 375VA cosÃâ= 0.6), 1.000.000 (30V DC / 2 A / 60 W), 2.000.000 (10V DC / 0.01 A / 0.1 W) |
| Number of outputs, signalling function, delayed, with contact | 0 |
| With feedback circuit | Yes |
| Suitable for monitoring of magnetic switches | Yes |
| Suitable for monitoring of proximity switches | Yes |
| Suitable for monitoring of emergency-stop circuits | Yes |
| Suitable for monitoring of optoelectronic protection equipment | Yes |
| Suitable for monitoring of position switches | Yes |
| Suitable for monitoring of tactile sensors | Yes |
| Suitable for monitoring of valves | Yes |
| Immediate safe dry No output | 2 |
| Rated impulse withstand voltage | 2500 V |
| Input simultaneity | Infinite |
| Switching current | 10 mA @ 10V |
| Resistive, DC-1 | 6.0 A @ 24V DC |
| Resistive, AC-1 | 6.0 A @ 250V AC |
| SIL according to IEC 61508 | 3 |
| With approval according to UL | Yes |
| Stop category according to IEC 60204 | 0 |
| Performance level according to EN ISO 13849-1 | Level e |
| Type of safety according to IEC 61496-1 | 4 |
| With approval for TUV | Yes |
| With detachable clamps | No |
| Rated control supply voltage at AC 50 Hz | 115 V |
| Rated control supply voltage at AC 60 Hz | 115 V |
| Terminal protection | IP20, DIN 0470 |
| Weight | 115/230V AC: 215 g (0.47 lb) |
| Vibration | 10…55 Hz, 0.35 mm |
| Shock | 10 g, 16 ms, 100 shocks |
| Rail mounting possible | Yes |
| Response time | 15 ms |
| Release delay | No |
| Recovery time | 100 ms |
| Enclosure protection | IP40 (NEMA 1) |
| MTTFd | 375 year |
| DC avg | 99 % |
| T cycle | 8/28800 (h/s) |
| Mission time | 20 year |
| Hours of operation | 24 h |
| Days of operation | 365 Days |
| Performance level | up to e |
| Operating temperature | -5 ðC |
| Relative humidity | Operating: 90% |
| Pollution degree | 2 |
| Enclosure type | IP40 (NEMA 1), DIN 0470 |
| PFHd | 2.03e-09 |
| Category | up to 4 |
| Height | 75 mm |
| Width | 22.5 mm |
| Depth | 110 mm |
| Mounting | DIN rail: 35 mm |
| Reset | Automatic/manual |