| certificates / approvals |
function display |
2 LED, green |
|---|---|
creepage distances and clearances between the circuits |
EN 60664-1 |
protection degree according to DIN EN 60529 (housing) |
IP40 |
protection degree according to DIN EN 60529 (terminals) |
IP20 |
ambient temperature min. |
-25 °C |
ambient temperature max. |
55 °C |
permissible torque min. |
0.5 Nm |
permissible torque max. |
0.6 Nm |
tightening moment |
0.6 Nm |
wire range cage clamp terminals |
2 x 0.25mm² – 1.5mm² |
weight |
0.12 kg |
standards |
EN ISO 13849-1EN 62061; EN 62061 |
suitable for safety functions |
yes |
with muting function |
no |
feedback circuit |
yes |
start contact |
yes |
stop category acc. to IEC 60204 |
0 |
rail mounting possible |
yes |
detachable clamps |
yes |
|---|---|
type of electric connection |
spring clamp connection |
category (ISO 13849-1) |
3 |
|---|---|
PL (ISO 13849-1) |
Level d |
SILCL (IEC 62061) |
2 |
PFHd (High demand mode) |
2 E-7 1/h |
HFT |
1 |
MTTFd |
58 a |
TM |
20 a |
proof test intervall (High demand mode) |
20 a |
model |
basic device |
|---|---|
suitable for monitoring of magnetic switches |
no |
suitable for monitoring of proximity switches |
yes |
suitable for monitoring of emergency-stop circuits |
yes |
suitable for monitoring of optoelectronic protection equipment |
no |
suitable for monitoring of position switches |
yes |
enabling paths |
normally open contact |
|---|---|
contact material |
Ag alloy |
rated switching voltage, enabling paths AC |
240 V |
rated switching voltage, enabling paths DC |
50 V |
max. thermal current Ith, enabling paths |
6 A |
max. total current I² of all current path |
9 A² |
application category AC-15 (NO) |
Ue 230V, Ie 3A |
application category DC-13 (NO) |
Ue 24V, Ie 3A |
short-circuit protection (NO), max. fuse insert |
6 A class gG fuse, fuse integral < 100 A²s |
mechanical life |
107 switching cycles |
outputs, safe, undelayed, with contact |
2 |
outputs, safe, delayed, with contact |
0 |
nominal output voltage DC |
24 V |
|---|---|
input current (safety circuit / reset circuit) |
50 mA |
max. peak current (safety circuit / reset circuit) |
70 mA |
response time tA1 |
20 ms |
response time tA2 |
70 ms |
min. switch-on time |
30 ms |
recovery time tW |
> 200 ms |
release time tR |
< 70 ms |
max. resistivity, per channel |
≤ (5 + (1.333 x UB / UN – 1) x 200) Ω |
type of switch function of the inputs |
normally open contact |
evaluation inputs |
1-channel |
nominal voltage UN |
AC/DC 24 V |
|---|---|
rated consumption AC |
2 VA |
rated consumption DC |
1 W |
rated frequency min. |
50 Hz |
rated frequency max. |
60 Hz |
operating voltage min. |
20.4 V |
operating voltage max. |
26.4 V |
electrical isolation supply circuit – control circuit |
no |
min. rated control supply voltage at AC 50 Hz |
20.4 V |
max. rated AC voltage for controls, 50 Hz |
26.4 V |
min. rated DC voltage for controls |
20.4 V |
max. rated DC voltage for controls |
26.4 V |
min. rated control supply voltage at DC |
20.4 V |
rated control supply voltage at AC 60HZ |
20.4 V |
rated control supply voltage at AC 50HZ |
26.4 V |
depth |
91.5 mm |
|---|---|
width |
22.5 mm |
height |
106.5 mm |
ECLASS 11 |
|
|---|---|
ECLASS 8.1 |
27371819 |
ETIM 9.0 |
EC001449 |
ETIM 8.0 |
EC001449 |
ETIM 7.0 |
EC001449 |
ETIM 6.0 |
EC001449 |
ETIM 5.0 |
EC001449 |
ETIM 4.0 |
EC001449 |
ETIM 3.0 |
EC001449 |
ROHS conformity status |
compliant/exempted |
|---|---|
ROHS exceptions |
III-7(c)I |
REACH-SVHC conformity status |
compliant |