Tecnichal data
| Degree of protection (IP) | IP67 |
| Shipping weight, approx | 10.4 kg |
| Shock | Operational: 15 G |
| Wire strip length | Power and ground terminals: 0.35 inch (9 mm) |
| Vibration | Operational, 1 G, 0.15 mm (0.006 inch) displacement |
| Tightening torque | Power and ground terminals: 4.5 lb.inch per UL/NEMA (secondary terminal) |
| Mechanical life operations | Output ratings (sourced from control circuit): 50000000 operations (18K operations/hr) |
| Disconnect lock out | Recommend 8 mm (5/16 inch) lock shackle or hasp. The hasp should not exceed 8 mm (5/16 inch) when closed. |
| Baud rates | 500 kBps |
| Overload current, max | 1.1 A |
| Communication | DeviceNet |
| DeviceNet input current surge | 15 A for 250 üs |
| Control module | Control module only |
| DeviceNet input current | 364 mA @ 11V DC – 4.0 W |
| Total with maximum sensor inputs (4) | 367 mA @ 24V DC – 8.8 W |
| Overvoltage category | Control circuit: III per IEC |
| Rated operating current | Power circuit: 2.5 A maximum |
| Rated impulsed voltage | Power circuit: 6 kV |
| DeviceNet supply voltage rating | Range 11…25V DC, 24V DC Nominal |
| Control (pick up) | Power requirements: 0.71 A without HOA |
| Control (hold in) | Power requirements: 0.063 A without HOA |
| Rated input operation voltage | 24V DC |
| Input OFF-state current | <1.5 mA |
| Input OFF-state voltage | 0…5V DC |
| Input ON-state voltage | 10…26V DC |
| Distance, max | 500 m (1630 ft) @ 125 kbps |
| Operating frequency | Power circuit: 50/60 Hz |
| Input ON-state current | 7.2 mA @ 24V DC |
| Option 1 | HAND-OFF-AUTO selector keypad with FORWARD and REVERSE |
| Number of contacts | Output rating- sourced from control circuit: 2 |
| Voltage status only | 11…25V DC from DeviceNet |
| Trip rating | 120% of full load current (FLC) setting |
| Total control power (pick up) with max outputs | External devices powered by control voltage: 65 W without HOA |
| Total control power (hold in) with max outputs | External devices powered by control voltage: 50 W without HOA |
| Input compatibility | IEC 1133 Type 1+ per IEC |
| Application in industrial area permitted (SCPD list) | Size per NFPA 70 (NEC) or NFPA 79 for group motor applications |
| Insulation voltage | Power circuit: rated 600V |
| Dielectric withstand | Power circuit: 2500V AC per IEC |
| Type of contacts | Output rating- sourced from control circuit: normally open (NO) |
| Outputs current (2) 1 A each, max | External devices powered by control voltage: 2 A without HOA |
| Current available | 50 mA maximum per input, 200 mA total |
| Type of control circuit | Output rating- sourced from control circuit: electromechanical relay |
| Conventional thermal current (Ith) | Output rating- sourced from control circuit: total of both outputs ââ°¤2 A |
| Circuit breaker operational current rating, max | 60 A @ 480V (with gland type: CR or DR) |
| RMS symmetrical amperes | 65 kA @ 480Y/277V (with gland type: RR) |
| Rated operation voltage | Power circuit: 200…575V |
| 3-phase power/motor cable connection | Round |
| Input filter – software selectable | Settable from 0…64 ms in 1 ms increments (ON to OFF) |
| Kind of current | Output ratings (sourced from control circuit): AC/DC (not to be used as an AC/DC power supply) |
| Fuse operational current rating, max | Time delay: 20 A @ 480Y/277V (with gland type: RR) |
| Total control power (pick up) | Power requirements: 17 W without HOA |
| Total control power (hold in) | Power requirements: 1.5 W without HOA |
| Trip class | Class 10, 15, 20 |
| Operational power rating | Reversing starters ââ¬Ã¢ IP67/Type 4/12: 1.5 Hp @ 575V AC, 60 Hz |
| Supporting protocol for DeviceNet | Yes |
| Application in industrial area permitted | Yes |
| Mains frequency | 50/60 Hz |
| Short circuit protection device performance (SCPD) type | Type 1 |
| Utilization category | Power circuit: AC-3 per IEC |
| External devices powered by DeviceNet | 50 mA – total 200 mA |
| Electrical life cycle | Output ratings (sourced from control circuit): 100000 operations (1.8K operations/hr) |
| Altitude | 2000 m |
| Operating temperature | -20 ðC |
| Storage and transportation temperature | -25 ðC |
| Humidity | 5…95% noncondensing |
| Protection against shock | Power circuit: IP2X per IEC |
| Surge transient | 1 kV L-L, 2 kV L-N (earth) |
| Radiated emissions | Class A, Group 1, equivalent to C2 emissions |
| Conducted radio frequency emissions | Class A |
| Radio frequency electromagnetic field | 10 V/m |
| Degree of protection (NEMA) | 4 |
| Pollution degree | 3 |
| Fast transient | 2 kV |
| Electrostatic discharge | 4 kV contact and 8 kV air |
| Wire size | Power and ground terminals: #16…#10 AWG per UL/NEMA (Primary/secondary terminal) |
| Number of poles | 3 |